HD67056-MSTP-XXX

Gateway BACnet MS/TP Slave / M-Bus Master
HD67056-MSTP-XXX

Interfaces:
1x RS485, 1x RS232, 1x M-Bus

DatasheetTechnical supportRequest/On-site presentation
  • Up to 1,500 BACnet objects
  • High temperature range from -40 °C to +85 °C
  • Up to 250 M-Bus devices can be connected
  • Galvanic isolation between serial and M-Bus
  • Transmission of project planning via Ethernet
Gateways und Protokollwandler Gateway BACnet MS-TP Slave M-Bus Master HD67056-MS-TP-PTP-XXX

The configurable gateway HD67056-MSTP-XXX enables communication between M-Bus devices (up to 250 M-Bus slaves) and a BACnet MS/TP master. You can use it to make the data points from all connected M-Bus slaves available to a BACnet MS/TP master. Transferring the configuration of the gateway by software via the RS232 port is very quick and easy. The M-Bus variables are provided as BACnet objects. The DIN rail mounting and screw terminals ensure quick and safe installation and problem-free wiring of the device.

Interfaces:

1x RS485 (screw terminal, 3-pin)
1x RS232 (Sub-D connector, 9-pin)
1x M-Bus (screw terminal, 2-pin)

BACnet objects:

Read and write up to 1,500 BACnet objects

Data rate M-Bus:

300 bps to 38,400 bps

LED:

4x signal display for supply and communication

Supply:

18 VDC to 35 VDC or
15 VAC to 21 VAC

Power consumption:

HD67056-MSTP-20: 3.5 watts / VA (without load), 4 watts / VA (with load)
HD67056-MSTP-40: 3.5 watts / VA (without load), 5 watts / VA (with load)
HD67056-MSTP-80: 3.5 watts / VA (without load), 8 watts / VA (with load)
HD67056-MSTP-160: 3.5 watts / VA (without load), 14 watts / VA (with load)
HD67056-MSTP-250: 3.5 watts / VA (without load), 30 watts / VA (with load)

Software:

Free configuration software SW67056 for
parameterization of the device.

BBMD functionality:

This gateway only supports BBMD in a rudimentary way. No "Registration by Foreign Devices" and no NAT.

M-Bus scan function:

The use of the scan function is only possible for devices from hardware version
C.S: B244/ B256/ B264 and the latest software version. For further questions and information, please read Technical Note 0105 M-Bus scan function.

Operating temperature:

-40 °C to +85 °C

Humidity:

10 % to 80 %, non-condensing

Housing:

PVC

Dimensions (WxHxD):

106 mm x 95 mm x 60 mm

Weight:

approx. 200 g

Fastening:

Mounting on the DIN rail

Note:

The article description should always be viewed from the gateway's perspective.

You can connect a master on the BAC-net side and a slave on the M-Bus side to the HD67056.

Customs tariff number:

8517 62 00

Manufacturer:

ADFweb.com S.r.l.

Broschüre Gateways 2025
Brochure / Safely connecting bus systems in industry & building management

Here you can download our Gateways brochure / Securely connecting bus systems in industry & building management.

Wachendorff Prozesstechnik
Electric mobility

Cost reduction thanks to gateways

Wachendorff Prozesstechnik
Elevator technology

Interference-free communication with gateways and repeaters

Installationsanleitung HD67056-B2-XXX
Installation instructions HD67056-MS/TP-XXX

Manual hd67059m
HD67056 M-Bus Master / BACnet/IP Slave - Gateway

sw-HD67514
SW67056

Free configuration software SW67056 for
parameterization of the device.

By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.

Technical Note Gateways
Technical Note 2201 Gateway commissioning

Technical Note Gateways
Technical Note 2102 Compositor project planning

copy / save / send

Technical Note Gateways
Technical Note 0105 M-Bus scan function

Integrated scan function for M-Bus gateways

FAQ
FREQUENTLY ASKED QUESTIONS
PICS Dokument HD67056
PICS document HD67056

The "Protocol Implementation Conformance Statement" called "PICS" document describes the BACnet functionalities of a BACnet application.

Netzgerät Hutschienen-Netzgerät AMR4-24
AMR4-24

DIN rail power supply AMR4-24

Single-phase input: 90 VAC to 264 VAC
Output: 24 VDC (2.5 A)
Operating temperature: -40 °C to +71 °C
Overload and overvoltage protection

Gateways und Protokollwandler M-Bus Scanner Auslesemodul HD67031-B2-XX
HD67031-B2-XX

M-Bus scanner / readout module
HD67031-B2-XX

Interfaces:
1x Ethernet port, 1x M-Bus master, 1x M-Bus slave

Article no.Article descriptionAvailablePrice/ItemNumber
HD67056-MSTP-20

Gateway BACnet MS/TP Slave / M-Bus Master
- for up to 20 M-Bus slaves

on request
HD67056-MSTP-40

Gateway BACnet MS/TP Slave / M-Bus Master
- for up to 40 M-Bus slaves

on request
HD67056-MSTP-80

Gateway BACnet MS/TP Slave / M-Bus Master
- for up to 80 M-Bus slaves

on request
HD67056-MSTP-160

Gateway BACnet MS/TP Slave / M-Bus Master
- for up to 160 M-Bus slaves

on request
HD67056-MSTP-250

Gateway BACnet MS/TP Slave / M-Bus Master
- for up to 250 M-Bus slaves

on request
AccessoriesAvailablePrice/ItemNumber
AMR4-24

DIN rail power supply unit for building automation, 90 to 264 VAC, 24 VDC, 2.5 A

on request
KABETH10

Patch cable, RJ45 UTP CCA, CAT5e white, 0.3 m

on request
KABETH11

Patch cable, RJ45 UTP CCA, CAT5e white, 1 m

on request
KABETH12

Patch cable, RJ45 UTP CCA, CAT5e white, 2 m

on request
= available from stock
= Delivery time approx. 1 week
= Please inquire about delivery time

Subject to prior sale