HD67042-A1

Gateway CAN / CANopen
HD67042-A1

Interfaces:
1x Ethernet port , 1x CAN , 1x CANopen

DatasheetTechnical supportRequest/On-site presentation
  • Configurable gateway for free variable management
  • High temperature range from -40 °C to +85 °C
  • Galvanic 3-way isolation between CAN / CANopen and power supply
  • Different baud rates possible in the segments
  • Bidirectional data exchange between CAN and CANopen
Gateways und Protokollwandler Gateway CAN-CANopen HD67042-A1

The configurable gateway HD67042-A1 enables communication between a CAN 2.0A or CAN 2.0B network and a CANopen network. This allows you to integrate the CAN data directly into a CANopen system with little effort. Communication from CANopen to CAN is also possible.
It can be easily configured via the Ethernet interface using the free SW67042 configuration software.
You assign SDO or PDO messages from the CANopen network to the CAN data. The gateway can send PDO messages when the value changes or cyclically. The DIN rail mounting and plug-in screw terminals ensure quick and safe installation and easy wiring of the device. Installation is simple and reliable on a DIN rail.

Interfaces:

1x CAN (removable screw terminal, 3-pin)
1x CANopen (removable screw terminal, 3-pin)
1x Ethernet port (RJ45 socket)

Data rate CAN/CANopen:

Max. 1 Mbps

Galv. separation:

> 2,000 VDC

LED:

4x signal display for supply and communication

Supply:

12 VDC to 35 VDC or
8 VAC to 24 VAC, 50/60 Hz

Power consumption:

3.5 Watt / VA

Software:

Free configuration software SW67042 for
parameterization of the device.

Operating temperature:

-40°C to +85°C

Humidity:

10% to 80%, non-condensing.

Housing:

Previous housing: PVC
New housing: PC-ABS

Dimensions (WxHxD):

Previous housing: 23 mm x 107 mm x 120 mm
New housing: 22.5 mm x 90.7 mm x 123 mm

Weight:

approx. 200 g

Fastening:

Mounting on the DIN rail.

Customs tariff number:

8517 62 00

Manufacturer:

ADFweb.com S.r.l.

Datenblatt
Data sheet HD67042A

Broschüre Gateways 2025
Brochure / Safely connecting bus systems in industry & building management

Here you can download our Gateways brochure / Securely connecting bus systems in industry & building management.

Wachendorff Prozesstechnik
Electric mobility

Cost reduction thanks to gateways

Wachendorff Prozesstechnik
Elevator technology

Interference-free communication with gateways and repeaters

Installationsanleitung HD67056-B2-XXX
Installation instructions HD67042-A1

Manual hd67042a
HD67042-A1 - Gateway CAN 2.0A & 2.0B / CANopen

Software HD67042
SW67042

Free configuration software for SW67042 for
parameterization of the device.

By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.

Technical Note Gateways
Technical Note 2201 Gateway commissioning

Technical Note Gateways
Technical Note 2102 Compositor project planning

copy / save / send

FAQ
FREQUENTLY ASKED QUESTIONS
Netzgerät Hutschienen-Netzgerät DRS3-24
DRS3-24

DIN rail power supply unit DRS3-24

Single-phase input: 85 VAC to 264 VAC
Output: 24 VDC
Output power of 72 watts (3 A)
Operating temperature: -25 °C to +71 °C
Overload and overvoltage protection

Article no.Article descriptionAvailablePrice/ItemNumber
HD67042-A1

Gateway CAN2.0A & CAN2.0B to CANopen

on request
AccessoriesAvailablePrice/ItemNumber
DRS3-24

Power supply unit for DIN rail, 85 to 264 VAC, 24 VDC 3 A, spring terminal

on request
DRS4-24A

Power supply unit for DIN rail, 85 to 264 VAC, 24 VDC 4.2 A, screw terminal

on request
AC34107

Null modem cable, socket/socket, 3 m long

on request
= available from stock
= Delivery time approx. 1 week
= Please inquire about delivery time

Subject to prior sale