Gateway BACnet/IP Server / Modbus TCP Client
HD67673-IP-A1
Interfaces:
2x Ethernet port
- Read and write up to 2,000 BACnet objects
- Bidirectional data exchange between BACnet and Modbus TCP
- High temperature range from -40 °C to +85 °C
- Galvanic isolation
- Transmission of project planning via Ethernet

Further information on this gateway is available on request. Please get in touch with the contact persons listed below.
Interfaces:
2x Ethernet port (RJ45 socket)
No physical network separation!
Note: The switch function between the Ethernet ports can be used to topologically connect separate networks.
BACnet objects:
Up to 2,000 BACnet objects configurable
Total memory: 1,438 bytes IN and 1,438 bytes OUT
Modbus data points:
512 read and 512 write
LED:
6x signal display for supply and communication
Supply:
12 VDC to 35 VDC or
8 VAC to 24 VAC
Power consumption:
HD67673-IP-A1: 3.5 Watt / VA
Supported function codes:
FC01, FC02, FC03, FC04, FC05, FC06, FC15, FC16
You can find more detailed information on this in
Technical Note 0302: Modbus basics
Software:
Free configuration software SW67673 for
parameterization of the device
BBMD functionality:
This gateway only supports BBMD in a rudimentary way. No "Registration by Foreign Devices" and no NAT.
Supported function codes:
01, 02, 03, 04, 05, 06, 15, 16
Operating temperature:
-40 °C to +85 °C
Humidity:
10 % to 80 %, non-condensing
Housing:
Previous housing: PVC
New housing: PC-ABS
Dimensions (WxHxD):
Previous housing: 23 mm x 107 mm x 120 mm
New housing: 22.5 mm x 90.7 mm x 123 mm
Weight:
approx. 200 g
Fastening:
Mounting on the DIN rail
Note:
The article description should always be viewed from the gateway's perspective.
You can connect masters to the HD67673 on the BACnet side and slaves on the Modbus TCP side.
Customs tariff number:
8517 62 00
Manufacturer:
ADFweb.com S.r.l.

Here you can download our Gateways brochure / Securely connecting bus systems in industry & building management.

Free configuration software SW67673 for
parameterization of the device.
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.

The "Protocol Implementation Conformance Statement" called "PICS" document describes the BACnet functionalities of a BACnet application.

DIN rail power supply unit DRS3-24
Single-phase input: 85 VAC to 264 VAC
Output: 24 VDC
Output power of 72 watts (3 A)
Operating temperature: -25 °C to +71 °C
Overload and overvoltage protection