FnIO module - MODBUS TCP/IP-
Fieldbus node, NA9289
establishes the connection between the FnIO system and the Modbus TCP/IP fieldbus
Delisting
If you have any questions, please contact our technical application consultants.
- Direct diagnostics via LEDs on the fieldbus node
- Replacement of modules when wiring is still in place
- Manages up to 63 expansion modules with 1, 2, 4, 8 and 16 channels
- Simple termination (no resistor or end module required)

As a slave, the NA9289 fieldbus node establishes the connection between the FnIO system and the Modbus TCP/IP fieldbus. The I/O modules used are automatically recognized and the fieldbus node creates a local process image.
The internal process image of the NA9289 fieldbus node is stored in the memory of the relevant controller via the Modbus TCP/IP fieldbus. By dividing the process image into an input and output data area, the process data is read in via the Modbus, processed further in a controller and the process output data is output via the Modbus.
The automatically generated process image is created in the order of the expansion modules in their slots.
Power supply:
Supply voltage: 24 VDC typical
Supply voltage range: 11 VDC to 28.8 VDC
Protection: Output current limitation (min. 1.5 A), reverse polarity protection
Power consumption:
100 mA typical at 24 VDC
Total current for the I/O modules:
1.5 A at max. 5 V
Isolation:
System voltage to internal logic: Not isolated
System voltage to I/O driver: Isolated
Field performance:
Supply voltage: 24 VDC typical (max. 28.8 VDC)
Supply voltage range: 11 VDC to 28.8 VDC
Max. Field power Contact:
10 ADC max.
Module dimensions (LxHxW):
54 mm x 99 mm x 70 mm
Node type:
Slave node (MODBUS/TCP, MODBUS/UDP server)
Number of extensions for I/O slots:
max. 63 slots
Input variable:
max. 252 bytes
Output variable:
max. 252 bytes
Max. length of bus cable:
Up to 100 m from the Ethernet hub/switch with
twisted CAT3 UTP/STP
Max. Number of nodes:
Limited by Ethernet specification
Baud rate:
10/100 MBit/s, auto-negotiation, full-duplex
Protocol:
MODBUS/TCP, MODBUS/UDP, DHCP, 10 TCP connections
Interface connector:
2x RJ-45
LED status display:
1x for module status display (MOD), green/red
1x for link status display (LINK), green
1x for active status (ACTIVE), green
1x for I/O expansion module status (I/O), green/red
1x for system voltage status, green
1x for field voltage status, green
2x for RJ-45 connection, yellow for link active and green not used
Serial interface:
RS-232 for Modbus/RTU, operating device or IOGuidePro
Serial interface configuration (RS-232):
Node: 1 (fixed)
Baud rate: 115200 (fixed)
Data bit: 8 (fixed)
Parity: none (fixed)
Stop bit: 1 (fixed)
IP address setting:
DHCP/BootP or IOGuidePro
IP address range:
xxx.xxx.xxx.1 to 253 (available range)
xxx.xxx.xxx.254 to 255 (reserved for IAP)
Protection class:
IP20

Configuration software for FnIO modules
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.
- Lab View
- C ++
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.
- Lab View
- C ++
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.

Here you can download our flyer "CODESYS - PLC - WebPanels a strong team for your application".