Signal converter pulse divider WZ112A
processes input pulses from a sensor and outputs them rescaled
3-way galvanic isolation
- Outputs a pulse for a definable number of input pulses
- Division factor adjustable via DIP switch
- Pulse width up to 500 ms can be used
- Can be used for all common sensors
- 19 VAC to 28 VAC / 19 VDC to 40 VDC Power supply
- 3-fold galvanic isolation supply/input/output
- Simple mounting on DIN rail

The WZ112A pulse divider processes the input signal from a sensor and outputs it rescaled. The devices can be easily adjusted using the DIP switches. The devices are simply snapped onto a DIN rail for installation.
Inputs:
All commercially available sensors (PNP, NPN, relay, Namur) can be connected via the input terminals.
Measuring principle:
Pulse counter.
Input frequency:
max. 400 Hz
Output:
One changeover relay max. 5 A, 250 VAC.
Power supply:
19 VDC to 40 VDC / 19 VAC to 28 VAC, max. 2.5 W
Setting:
A division factor of 0 to 256 can be set via DIP switches. The maximum pulse width is 500 ms. The pulse width of the output can be continuously adjusted from 100 ms to 500 ms via a potentiometer.
Ambient conditions:
Operation: 0 °C to +50 °C,
Storage: -20 °C to +70 °C,
30 % to 90 % relative humidity at 40 °C.
Connection:
via plug-in screw terminals.
Safety:
EN61010-1:2013-10
EMC:
EN61000-6-2:2006-10
EN61000-4-4:2013-01
EN61000-6-4:2007-11 + A1:2013-01
EN61000-4-5:2015-05
EN61000-4-2:2011-04
EN61000-4-6:2014-09
EN61000-4-3:2007-04 + A1:2009-01 + A2:2011-01
EN61000-4-11:2006-02
Housing:
Sturdy plastic housing
Isolation:
1.5 kV between supply/input and 4 kV to the output.
Dimensions:
W 17.5 mm x H 100 mm x D 112 mm
Weight:
approx. 200 g
Scope of delivery:
Device, operating instructions
Manufacturer:
Seneca s.r.l.

You can download the handout Signal converter here.