WZ203

Signal converter for alternating variables WZ203
This product is discontinued

Please contact our application consultants, we will be happy to advise you on alternatives.

converts 0 VAC to 500 VAC, 35 Hz to 75 Hz into voltage: 0 VDC to 10 VDC, 0/1 VDC to 5 VDC, current: 0/4 mA to 20 mA
RS232 / RS485 interface
3-way galvanic isolation

DatasheetTechnical supportRequest/On-site presentation
Signalwandler WZ203

Channels

1 input
0 VAC to 500 VAC
50/60 Hz

1 output
Voltage range: 0 VDC to 10 VDC, 0/1 VDC to 5 VDC
Current range: 0/4 mA to 20 mA

Resolution

12 bit

Accuracy

0,25 %

Linearity

0,1 %

Temperature coefficient

0,02 % / °K

Insulation

Galvanic 3-way isolation,
Test voltage 1.5 kV between supply and output.
3.7 kV between signal input and output.

Supply

10 VDC to 40 VDC,
19 VAC to 28 VAC(50 Hz to 60 Hz),
max. 2 W

Setting

DIP switch

Scaling

Vrms. (Vrms), Ieff. (Irms),
Power (Watt), cosf, VAR

Display

LED: Fault / settings

Assembly

35 mm DIN rail

Ambient conditions

Working temperature: -10 °C to +65 °C
Storage temperature: -20 °C to +85 °C
Humidity: 30 % to 90 % non-condensing

Dimensions (W x H x D)

17.5 mm x 100 mm x 112 mm

Weight

approx.: 200 g

Datenblatt
Data sheet WZ203

Datenblatt
Data sheet WZPC-BUS

info Signalwandler-Broschüre
Signal converters and monitoring modules

You can download the handout Signal converter here.

Food

Quality control and traceability

Manual WZ203
WZ203 Single-phase network analyzer