FnIO module - 8-channel resistance thermometer input module ST3708
allows the direct connection of resistance thermometers (RTD) in 2-/3-wire connection technology
Delisting
If you have any questions, please contact our technical application consultants.
- The resistance thermometer input module allows the direct connection of Pt and Ni resistance sensors.
- Common reference potential of the channels AGND.

The 8-channel resistance thermometer input module allows the direct connection of Pt resistance sensors and resistors. The connection can be made using 2-/3-wire technology. Linearization over the entire temperature range is handled by the bus terminal. A short circuit or interruption of the sensor cable as well as an out-of-range condition is indicated by a red error LED.
Isolation:
I/O to control logic: Optocoupler
Power consumption:
max. 100 mA at 5 VDC
Field voltage:
not used, field voltage bypass to the
next expansion module
Cabling:
Module connector, ribbon cable 20-pin, 2m
(KABST20A)
Dimensions (LxHxW):
12 mm x 99 mm x 70 mm
Operating temperature:
0 °C to 55 °C
Operating altitude:
max. 2,000 m
Assembly:
DIN rail
Number of inputs:
8 channels
Indicators:
1 x green / red for module status display, 8 x green for input status display
input status display
Sensor types:
Pt50, Pt100, Pt200, Pt500, Pt1000, JPt50, JPt100, JPt200, JPt500, JPt1000, Ni100, Ni200, Ni500, Ni1000, Ni120, NI 1000LG,
Resistance (100 mOhm/bit, 10 mOhm/bit, 20 mOhm/bit, 50 mOhm/bit).
Resolution:
± 0.1 °C or 10 mOhm
Conversion time:
30 ms/ 1 channel typical