Signal splitter WZ170REG1
Converts a standard signal into 2 galvanically isolated standard signals
4-fold galvanic isolation
- Universal input for current/voltage signals, potentiometers, Pt100, Pt500, Pt1000, Ni100, thermoresistors and
- thermocouples type J, K, R, S, T, B, E, N
- Output: 2 channels 0/4 mA to 20 mA and 0 V to 10 V
- Power supply: 10 VDC to 40 VDC or 19 VAC to 28 VAC
- 4-fold galvanic isolation (supply/input/2xoutput)
- Simple programming via DIP switches or software

The WZ170REG1 signal splitter converts current/voltage signals, signals from temperature sensors as well as resistance signals and potentiometer signals into 2 galvanically isolated current or voltage standard signals. With its DIP switches and the free EasySetup software (available in the Wachendorff Prozesstechnik download area), the converter can be easily parameterized.
easily parameterized. The device is simply snapped onto the DIN rail for installation.
Entrance:
Voltage adjustable from 0 V to 10 V
(input impedance: 120 Ohm)
Current adjustable from 0 mA to 20 mA
(internal shunt: 50 Ohm).
Potentiometer (active/passive) scalable range from
1kOhm to 100 kOhm configurable (with external, parallel resistor
resistor R= 330 Ohm).
Thermocouples of type: J, K, R, S, T, B, E and N.
Temperature-dependent resistors: Pt100, Pt500, Pt1000,
Ni100 (for 2-, 3-, 4-wire sensors).
Power supply:
10 VDC to 40 VDC or 19 VAC to 28 VAC (50 Hz to 60 Hz).
Output:
2 adjustable channels with
voltage: 0 V to 10 V (smallest resistor to be used
resistance = 20 kOhm )
Current: 0/4 mA to 20 mA (largest resistor to be used = 600 Ohm, max.
resistance = 600 Ohm, max. 13 V)
Response time:
adjustable: 11 ms, 22.66 ms (at 60 Hz) and 26 ms (at 50 Hz)
Resolution:
14 Bit
Accuracy:
For all input signals 0.1 %.
Environment controls:
Operation: -10 °C to +65 °C max. 90 % rH.
Storage: -20 °C to +85 °C.
Connection:
Pluggable screw terminals
Housing:
Sturdy plastic housing
Isolation:
Galvanic 4-way isolation between supply / input / output 1 and output 2 .
input / output 1 and output 2 . Protection: 1.5 KV between input
input and the outputs for one minute.
Protection class:
IP20
Electromagnetic compatibility, CE conformity:
- Interference emission: EN 61000-6-4
- Interference immunity: EN 64000-6-2
- Safety: EN 61010-1
Dimensions (LxWxH):
17.5 mm x 100 mm x 112 mm
Weight:
approx. 200 gram
Scope of delivery:
Device, operating instructions
Manufacturer:
Seneca s.r.l.

You can download the handout Signal converter here.

Configuration software for signal converters.
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.