Analog input module current - CSINI8
8 unsymmetrical channels 0/4 mA to 20 mA.
Delisting
If you have any questions, please contact our technical application consultants.
- 8 unsymmetrical channels 0/4 mA to 20 mA
- Cost-effective and fast replacement through hot swap
- Automatic addressing minimizes configuration time
- Configuration via Windows software

The new modular controller series consists of a master module and up to 16 different slave modules. The data acquisition modules can be combined with up to 15 other modules, so that a maximum of 128 measuring points can be acquired. Thanks to the innovative design, it is possible to replace a module without removing the power supply and without reconfiguration (hot swap). This significantly reduces downtime in the event of a module failure.
The acquisition modules are configured so that they can process a wide range of input signals from the field of thermocouples, Pt 100 and standard signals with a 16-bit resolution. Simple programming via clear software rounds off the overall picture.
The 10 Base-T Ethernet interface of the master module also enables the network connection of this new innovative series.
Inputs
8 unsymmetrical channels
0/4 mA to 20 mA
Maximum continuous overload current: 100 mA
Accuracy
±0.1 % of the display range
Scaling
±30,000 programmable
Resolution
16 bit
Linearization
100 points (CSINI8L0 only)
Sampling rate
50 ms to 400 ms depending on the number of inputs used.
Interfaces
Communication via CS master
Memory
Non-volatile memory for all program parameters.
Master module also saves the parameters.
Indicators
LEDs:
Status
alarm
Input error
Insulation
500 Vrms for 1 minute between supply and signal inputs.
Supply
Via base connector of the master module.
Replacement possible when supply voltage is applied.
Ambient conditions
Working temperature: 0 °C to +50 °C
Storage temperature: -40 °C to +85 °C
Weight
170 g
Assembly
35 mm DIN rail
Housing
Flame and scratch-resistant plastic housing.