TNM230

Multifunction measuring device TNM230

This product is discontinued.
Eight-channel energy and power meter with graphical display and web server

DatasheetTechnical supportRequest/On-site presentation
  • Energy meter
  • 8 channels / 24 conductors
  • Graphical display
  • WebServer
  • Top hat rail mounting
  • Sampling rate 1600 /s
  • Supported current ranges 1 A, 5 A, 0.333 V
  • Determination of harmonics"
Multifunktionsmessgerät TNM230

The TNM230 is a universal multifunctional measuring device with 8 channels, each with three phases. By using a TNM230 energy and power meter, the use of 7 additional energy meters or multifunctional meters can be saved, making the working environment clearer and space-saving, as the TNM230 energy and power meter covers the capacity of 8 energy meters or multifunctional meters. It has an RS485 and TCP/IP interface with the BACnet and Modbus protocols. The meter can be operated and configured via a web browser using the TCP/IP interface. An indispensable aid for any energy management system for displaying the minimum and maximum values, as well as the active and reactive power and all important measured variables.

Protocols / Interfaces

BACnet MS/TP and TCP/IP, Modbus RS485 and TCP/IP

Supply voltage

90 to 250 VAC, 50 / 60 Hz, 110 to 280 VDC

Dimensions (W x H x D)

300 mm x 110 mm x 65 mm

Weight

650 g

Power consumption

11 VA

Accuracy

Active power 0.2 %, reactive power 0.2 %

Display

320 x 240 color display

IP protection class

IP20

Operating temperature range

-20 °C to 70 °C

Storage temperature range

-20 °C to 70 °C

Application range relative humidity

0 % to 95 % RH

Sampling rate

1600

Number of channels / conductors

8 / 24, 8 / 32

Harmonics

32

Measurement type

Transducer measurement

Supported converters

0.333 V, 1 A, 5 A

Current measurement

0.1 A to 6 A

Measurement current - overload (RMS constant)

50 A

Current measurement - short-term (for 1 minute)

100 A

Measurement current - load

< 0.05 VA

Neutral current measurement

Not possible

Voltage measurement L-L

0.1 to 950 V

Voltage measurement L-N

0 to 550 V

Measurement voltage L-N - maximum (RMS constant)

1000 V

Measurement voltage L-N - load

< 0,06 V

Frequency measurement

45 to 65 Hz

Power factor measurement (cap./ind.)

-1 + 1

Current display range

0.0010 A to 99999 kA

Display range neutral current

Not possible

Display range voltage L-L

0.10000 V to 999999 kV

Display range voltage L-N

0.10000 V to 999999 kV

Display range Frequency

45.001 to 65.001 Hz

Display range Power factor (cap./ind.)

-1 + 1

Display range active power total/phase

0.10000000 W to 999999999 MW

Display range reactive power total/phase

0.10000000 VAR to 999999999 MVAR

Display range Apparent power total/phase

0.10000000 VA to 999999999 MVA

Display range active energy total/phase

0.100000 WH to 9999999 MWH

Display range Reactive energy total/phase

0.100000 VARH to 9999999 MVARH

Display area Apparent work total/phase

0.100000 VAH to 9999999 MVAH

Display range Total harmonic distortion V/I

Not possible

Display range Partial harmonic distortion V/I

Not possible

Functions

Alarm memory, alarms, data logging, easy-to-use menus, built-in tariff counter, graphical display of harmonics, multilingualism, minimum/maximum determination, fast trend displays, waveform display

Normative standards

EN 55022, class A, supplements A1; A2 EN 55024, supplements A1; A2 EN 61000-3-2, class A, EN 61000-3-3, supplements A1 EN 61000-4-2 EN 61000-4-3, EN 61000-4-4 EN 61000-4-5 EN 61000-4-6, EN 61000-4-11 IEC 62052-11 IEC 62053-22, IEC 62053-23

Scope of delivery

Multifunction measuring device

Manufacturer

Celsa Messgeräte GmbH

Schnittstellenbeschreibung TNM
Interface description Modbus & BACNET Communication with TNM PowerMeters

Energiedatenerfassung
Energy data acquisition

... You can only optimize what you measure!

Multifunktionsmessgeräte 20200810
Multifunctional measuring devices

Overview of product variants