Gateway BACnet/IP Server / M-Bus Master
HD67056-B2-XXX
Interfaces:
1x Ethernet port, 1x M-Bus
- Up to 1,500 BACnet objects
- High temperature range from -40 °C to +85 °C
- Up to 250 M-Bus devices can be connected
- Galvanic isolation between Ethernet and M-Bus
- Transmission of project planning via Ethernet

The configurable gateway HD67056-B2-XXX enables communication between M-Bus devices (up to 250 M-Bus slaves) and a BACnet/IP master. You can use it to make the data points from all connected M-Bus slaves available to a BACnet/IP master. Transferring the configuration of the gateway by software via the Ethernet port is very quick and easy. The M-Bus variables are provided as BACnet objects. The top-hat rail mounting and the screw terminals ensure quick and safe installation as well as problem-free wiring of the device.
Interfaces:
1x Ethernet port (RJ45 socket)
1x M-Bus (screw terminal, 2-pin)
BACnet objects:
Up to 1,500 BACnet objects
Data rate M-Bus:
300 bps to 38,400 bps
LED:
4x signal display for supply and communication
Supply:
18 VDC to 35 VDC or
15 VAC to 21 VAC
Power consumption:
HD67056-B2-20: 3.5 Watt / VA (without load), 4 Watt / VA (with load)
HD67056-B2-40: 3.5 watts / VA (without load), 5 watts / VA (with load)
HD67056-B2-80: 3.5 watts / VA (without load), 8 watts / VA (with load)
HD67056-B2-160: 3.5 watts / VA (without load), 14 watts / VA (with load)
HD67056-B2-250: 3.5 watts / VA (without load), 30 watts / VA (with load)
Software:
Free configuration software SW67056 for
parameterization of the device.
BBMD functionality:
This gateway only supports BBMD in a rudimentary way. No "Registration by Foreign Devices" and no NAT.
M-Bus scan function:
The use of the scan function is only possible for devices from hardware version
C.S: B244/ B256/ B264 and the latest software version. For further questions and information, please read Technical Note 0105 M-Bus scan function.
Operating temperature:
-40 °C to +85 °C
Humidity:
10 % to 80 %, non-condensing
Housing:
PVC
Dimensions (WxHxD):
71 mm x 95 mm x 60 mm
Weight:
approx. 200 g
Fastening:
Mounting on the DIN rail
Note:
The article description should always be viewed from the gateway's perspective.
You can connect slaves to the HD67056-B2-XXX on the M-Bus side and masters on the BACnet side.
BBMD functionality
This gateway does not support BBMD functionality.
Customs tariff number:
8517 62 00
Manufacturer:
ADFweb.com S.r.l.

Here you can merge our flyer Gateways / bus systems and data


Free configuration software SW67056 for
parameterization of the device.
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.

Integrated scan function for M-Bus gateways



The "Protocol Implementation Conformance Statement" called "PICS" document describes the BACnet functionalities of a BACnet application.

DIN rail power supply AMR4-24
Single-phase input: 90 VAC to 264 VAC
Output: 24 VDC (2.5 A)
Operating temperature: -40 °C to +71 °C
Overload and overvoltage protection
M-Bus scanner / readout module
HD67031-B2-XX
Interfaces:
1x Ethernet port, 1x M-Bus master, 1x M-Bus slave