PAXLI power indicator
3 1/2 digit digital display for alternating or direct current.
- PAX Lite series digital displays
- Large series of robust digital displays for many areas of automation technology
- individual backlit physical unit
- Simple scaling via spindle potentiometer
- Robust injection-molded plastic housing
- high degree of protection IP 65

PAXLITE devices are used in mechanical and plant engineering, the chemical industry, the plastics industry, the food industry, packaging and conveyor technology and in many other areas, where they help to automate and simplify work processes. All physical quantities recorded by a transducer that provides an output for mA, mV, VDC, VAC, ADC or AAC can be scaled and displayed in the desired physical unit.
Entrance areas
PAXLID:
±199.9 µADC,
±1.999 mADC,
±19.99 mADC,
±199.9mADC,
±1.999 ADC,
±199.9 mVDC
PAXLIA:
0 to 199.9 µAAC,
0 to 1.999 mAAC,
0 to 19.99 mAAC,
0 to 199.9mAAC,
0 to 1.999AAC,
0 to 199.9mVAC
Inputs
Quantities measured with a transducer that provides an analog output can be scaled via potentiometers and displayed in the desired unit. The selection is made via jumpers and the device has an automatic zero point correction.
Display
3½-digit, 14 mm high LED.
Accuracy
PAXLID00:
199.9 µA/199.9 mV, 1.999 mA, 19.99 mA:
+(0.1 % of the display + 1 digit)
199.9 mA: +(0.15 % of the display + 1 digit)
1.999 A: +(0.5 % of the display + 1 digit)
PAXLIA00 (45-500 Hz):
199.9 µA/199.9 mV
(0.1 % of the display + 2 digits)
199.9 mA: (0.15 % of the display + 2 digits)
1 A: (0.5 % of the display + 2 digits)
Maximum load
Display of overrange by flashing the last 3 digits
199.9 µA to 19.99 mA: 10 times the value of the range;
199.9 mA: 1A; 1.999 A: 3A
Scaling:
If there is a linear relationship between the signal input voltage and the parameter, the devices can be scaled so that the parameter is displayed directly. For this purpose, the applied voltage is also fed via a potentiometer on the rear for fine adjustment. An automatic zero point correction takes place.
Measuring rate
2.5 measurements/second
Decimal point setting
The setting is made via 3 DIP switches located in the device.
Backlit unit
A physical unit can easily be attached behind the display. With the label sheet, which contains all the usual units, the user can easily realize his desired unit backlit.
Power supply
115/230 VAC, +10%, 50/60 Hz, 6 VA, switchable
Protection class
Jet-proof and dust-tight to IP 65 from the front
Housing
Robust plastic housing.
W 96 mm x H 49 mm x D 107/164 mm. Panel cut-out
DIN 92 mm x 45 mm. Mounting via mounting frame with clamping screws.
Connection:
Via terminal strip on the rear.
Ambient temperature:
Operation: 0 °C to +60 °C.
Storage: -40 °C to +80 °C.
Weight:
approx. 540 g
Scope of delivery:
Device, fixing material, seal, operating instructions.
Customs tariff number:
9030 33 70
Manufacturer:
Red Lion Controls, USA.

How photovoltaics becomes economical

Price-efficient digital displays for mass flow measurement

Digital displays in the tensile force measurement

Filter monitoring via two separate channels - flexible and accurate