FnIO module - DeviceNet fieldbus node NA9112
establishes the connection between the FnIO system and the DeviceNet fieldbus
Delisting
If you have any questions, please contact our technical application consultants.
- Direct diagnostics via LEDs on the fieldbus node
- Replacement of modules when wiring is still in place
- Manages expansion modules with 1, 2, 4, 8 and 16 channels
- Simple termination (no resistor or end module required)
- Free combination of digital and analog I/Os & special functions

As a slave, the NA9112 fieldbus node establishes the connection between the FnIO system and the DeviceNet.
The I/O modules used are automatically recognized and the fieldbus node creates a local process image. The order of the analog expansion modules (data exchange word by word) and digital expansion modules (data exchange bit by bit) is arbitrary and can be mixed.
be mixed. The internal process image of the NA9112 fieldbus node is stored in the memory of the relevant controller via the DeviceNet. By dividing the process image into an input and output data area, the process data is read in via the DeviceNet, processed in a controller and the process output data is output via the DeviceNet.
The automatically generated process image is created in the order of the expansion modules in their slots. The bits of the digital expansion modules are combined into bytes and appended to the analog data. If the number of digital I/Os exceeds 8 bits, an additional byte is started by the fieldbus node.
Power supply:
Supply voltage: 24 VDC typical
Supply voltage range: 11 VDC to 28.8 VDC
Protection: Output current limitation (min. 1.5 A), reverse polarity protection
Power consumption:
30 mA typical at 24 VDC
Current consumption of the I/O module:
max. 1.2 A at 5 VDC
Isolation:
Power supply of the I/O driver: Not isolated
Field performance:
Supply voltage: 24 VDC nominal
Supply voltage range: 11 VDC to 28.8 VDC
Reverse polarity protection: -28.8 VDC
Max. Field power Contact:
max. 10 ADC
Weight:
155 g
Module dimensions (LxHxW):
42 mm x 99 mm x 70 mm
Interface specifications:
Number of nodes:
max. 64 nodes
Network protocol:
I/O slave message (group 2 slave only), poll command, bit-strobe command, cyclic command, COS command
Number of extensions for I/O slots:
max. 32 slots
I/O data size NA9112:
Total: Input 252 bytes, output 252 bytes
- Max. digital I/Os: Input 2016 channels, output 2016 channels
- Max. analog I/Os: Input 126 channels, output 126 channels
Display:
1x green/red for module status display (MOD)
1x green/red for network status display (NET)
1x green/red for expansion module status display (I/O)
1x green for field power status display (FieldPower)
Baud rate:
125 kBit/s (max. 500 m), 250 kBit/s (max. 250 m) 500 kBit/s
(max. 100 m), automatic baud rate selection
Module position:
Fieldbus node module, left side of the FnIO system
DeviceNet input voltage range:
11 VDC to 25 VDC
Field voltage monitoring:
Detects field voltage at 11 VDC

GSD file for Device Net
By downloading and using software and apps from this homepage, I agree to the GTC and the supplementary software clause.


Configuration software for FnIO modules
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.


Here you can download our flyer "CODESYS - PLC - WebPanels a strong team for your application".