Universal signal converter bipolar WZ109REGB
converts signals from V, mA, potentiometer, PT100, PT1000, PT500, Ni100, KTY81/84, NTC and thermocouples into a standard current or voltage signal,
3-way galvanic isolation
with bipolar output
- For current and voltage signals, potentiometers, Pt100, Pt500, Pt1000, Ni100, KTY81, NTC, KTY84-130/-150 and thermocouples type J, K, R, S, T, E, B and N
- Galvanic 3 - way isolation
- Converts the input signals into a -20 mA to +20 mA or -10 V to +10 V signal
- Supply via 10 VDC to 40 VDC or 19 VAC to 28 VAC
- Mini-USB interface
- Simple commissioning via DIP switch or software

The WZ109REGB universal signal converter converts current/voltage signals, signals from temperature sensors as well as resistance signals and potentiometer signals into a bipolar current or voltage signal. The output signal is linearly proportional to the input. The device is fully set via DIP switches and/or software on the PC and is immediately ready for operation. The WZ109REGB is simply snapped onto a top-hat rail for installation.
Entrance:
- Thermocouples J, K, R, S,T, E,Bund N.
- Temperature-dependent resistors (RTD) Pt100, Pt500, Pt1000, Ni100
- Potentiometer min. 500 Ohm, max. 100 kOhm.
- Voltage ±75m V to ±20 VDC
- Current -20 mADC to +20 mADC
- Rheostat (KTY81, KTY84-130/-150, NTC), min. 500 Ohm, max. 25 kOhm
Output:
-20 mA to +20 mA and
-10 V to +10 V
Response time:
35 msec with 11 bit resolution,
140 ms with 16-bit resolution (for voltage, current and potentiometer)
Resolution:
Programmable from 11 bits + sign to 15 bits + sign.
Power supply:
10 VDC to 40 VDC
19 VAC to 28 VAC, 50/60 Hz, max. 2 W
Accuracy:
between +/- 0.1 % and +/- 0.5 % depending on the range
Configuration via DIP switch:
- Input type
- Zero point and slope
- Output type
- Inversion of the output signal
About EASY SETUP software:
- Scaling, filter
- Sensor break detection
- Analog output value in case of error
- Interference frequency suppression (50 Hz to 60 Hz)
- Sampling rate/resolution
- Pt100 measurement via 2-, 3- or 4-wire
Protection:
Safety according to EN61010-1.
1,500 VAC between supply/input and output.
Ambient conditions:
Operation: -20 °C to +65 °C, 30 % to 90 % relative humidity.
Storage temperature: -20 °C to +85 °C.
Safety:
EN61010-1:2013-10
EMC:
EN61000-6-2:2006-10
EN61000-4-4:2013-01
EN61000-6-4:2007-11 + A1:2013-01
EN61000-4-5:2015-05
EN61000-4-2:2011-04
EN61000-4-6:2014-09
EN61000-4-3:2007-04 + A1:2009-01 + A2:2011-01
EN61000-4-11:2006-02
Connection:
Plug-in screw terminals.
Housing:
Sturdy plastic housing
Dimensions (WxHxD):
17.5 mm x 112 mm x 100 mm
Weight:
approx. 200 g.
Scope of delivery:
Device, operating instructions.
Manufacturer:
Seneca s.r.l.

You can download the handout Signal converter here.

Configuration software for signal converters.
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.