WZ109REGB

Universal signal converter bipolar WZ109REGB

converts signals from V, mA, potentiometer, PT100, PT1000, PT500, Ni100, KTY81/84, NTC and thermocouples into a standard current or voltage signal,
3-way galvanic isolation
with bipolar output

DatasheetTechnical supportRequest/On-site presentation
  • For current and voltage signals, potentiometers, Pt100, Pt500, Pt1000, Ni100, KTY81, NTC, KTY84-130/-150 and thermocouples type J, K, R, S, T, E, B and N
  • Galvanic 3 - way isolation
  • Converts the input signals into a -20 mA to +20 mA or -10 V to +10 V signal
  • Supply via 10 VDC to 40 VDC or 19 VAC to 28 VAC
  • Mini-USB interface
  • Simple commissioning via DIP switch or software
Universalsignalwandler bipolar WZ109REGB

The WZ109REGB universal signal converter converts current/voltage signals, signals from temperature sensors as well as resistance signals and potentiometer signals into a bipolar current or voltage signal. The output signal is linearly proportional to the input. The device is fully set via DIP switches and/or software on the PC and is immediately ready for operation. The WZ109REGB is simply snapped onto a top-hat rail for installation.

Entrance:

  • Thermocouples J, K, R, S,T, E,Bund N.
  • Temperature-dependent resistors (RTD) Pt100, Pt500, Pt1000, Ni100
  • Potentiometer min. 500 Ohm, max. 100 kOhm.
  • Voltage ±75m V to ±20 VDC
  • Current -20 mADC to +20 mADC
  • Rheostat (KTY81, KTY84-130/-150, NTC), min. 500 Ohm, max. 25 kOhm

Output:

-20 mA to +20 mA and
-10 V to +10 V

Response time:

35 msec with 11 bit resolution,
140 ms with 16-bit resolution (for voltage, current and potentiometer)

Resolution:

Programmable from 11 bits + sign to 15 bits + sign.

Power supply:

10 VDC to 40 VDC
19 VAC to 28 VAC, 50/60 Hz, max. 2 W

Accuracy:

between +/- 0.1 % and +/- 0.5 % depending on the range

Configuration via DIP switch:

  • Input type
  • Zero point and slope
  • Output type
  • Inversion of the output signal

About EASY SETUP software:

  • Scaling, filter
  • Sensor break detection
  • Analog output value in case of error
  • Interference frequency suppression (50 Hz to 60 Hz)
  • Sampling rate/resolution
  • Pt100 measurement via 2-, 3- or 4-wire

Protection:

Safety according to EN61010-1.
1,500 VAC between supply/input and output.

Ambient conditions:

Operation: -20 °C to +65 °C, 30 % to 90 % relative humidity.
Storage temperature: -20 °C to +85 °C.

Safety:

EN61010-1:2013-10

EMC:

EN61000-6-2:2006-10
EN61000-4-4:2013-01
EN61000-6-4:2007-11 + A1:2013-01
EN61000-4-5:2015-05
EN61000-4-2:2011-04
EN61000-4-6:2014-09
EN61000-4-3:2007-04 + A1:2009-01 + A2:2011-01
EN61000-4-11:2006-02

Connection:

Plug-in screw terminals.

Housing:

Sturdy plastic housing

Dimensions (WxHxD):

17.5 mm x 112 mm x 100 mm

Weight:

approx. 200 g.

Scope of delivery:

Device, operating instructions.

Manufacturer:

Seneca s.r.l.

info Signalwandler-Broschüre
Signal converters and monitoring modules

You can download the handout Signal converter here.

Food

Quality control and traceability

sw easy setup
Easy Setup

Configuration software for signal converters.

By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.

Manual WZ109REG
Universal signal converter bipolar WZ109REGB

Article no.Article descriptionAvailablePrice/ItemNumber
WZ109REGB

Universal signal converter
10 VDC - 40 VDC / 19 to 28 VAC

on request
AccessoriesAvailablePrice/ItemNumber
KABUSBM2

USB programming cable, USB 2.0A to micro USB, 2 m cable

on request
= available from stock
= Delivery time approx. 1 week
= Please inquire about delivery time

Subject to prior sale

Prices exclude 19% VAT and shipping costs.