WK112

Universal digital galvanic isolator WK112

Separates a digital signal from a
switch according to IEC1131 - Type 1,
2- or 3-wire NPN / PNP with 12 V or 22 V galvanic isolation.
Galvanic 2-way isolation

DatasheetTechnical supportRequest/On-site presentation
  • Galvanically isolates a digital signal from a NAMUR, phototransistor, IEC1131 - Type 1 switch, AICHI, reed
  • Isolates 2- or 3-wire NPN / PNP with 12 V or 22 V galvanically.
  • Two simultaneous PNP, NPN outputs
  • Own sensor supply
  • Supply via input terminals or K-bus rail
  • Slim 6.2 mm housing
  • Simple commissioning via DIP switches
  • Galvanic 2-way isolation
Universeller digitaler galvanischer Trenner WK112

The universal digital galvanic isolator WK112 galvanically isolates digital signals from switches according to IEC1131 - Type 1, NAMUR, phototransistor 2- or 3-wire NPN / PNP with 12 V or 22 V, reed and AICHI. Galvanic isolation prevents damage to the control unit due to overvoltage, interference or a defective sensor. The device is fully set via DIP switches and is immediately ready for operation. The signals in the output/power supply are completely galvanically isolated from the input. The WK112 is simply snapped onto a top-hat rail for installation.

Entrance:

NAMUR, phototransistor (impedance 1 kOhm), reed, AICHI,
Switch according to IEC1131 - Type 1, 2- or 3-wire NPN / PNP with 12 V or
22 V adjustable via DIP switch, maximum 400 Hz, maximum 28 V.

Sensor supply:

8V ±0.6 V, 12 V ±1 V and 22 V ±2 V with 22 mA
continuous load (approx. 35 mA peak). Sensor supply approx. 40 Ohm impedance.

Output:

2 simultaneous outputs, 1x PNP, 1x NPN, maximum 200 mA
per output, 30 V permanent and 50 V peak. Protected via a
self-repairing fuse.

Supply:

19.2 VDC to 30 VDC, power is supplied via the terminals or via the K-bus.

Short-circuit resistance:

1,500 VAC between input and supply/output 2-way.

Safety:

EN61010-1:2013-10

EMC:

EN61000-6-2:2006-10
EN61000-4-4:2013-01
EN61000-6-4:2007-11 + A1:2013-01
EN61000-4-5:2015-05
EN61000-4-2:2011-04
EN61000-4-6:2014-09
EN61000-4-3:2007-04 + A1:2009-01 + A2:2011-01
EN61000-4-11:2006-02

Ambient conditions:

0 % to 90 % relative humidity
Operation: -10 °C to +65 °C.
Storage: -40 °C to +85 °C

Connection:

Spring terminals from 0.2 mm² to 2.5 mm².

Housing:

Robust plastic housing made of PBT.

Protection:

IP20

Dimensions (WxHxD):

6.2 mm x 102.5 mm x 93.1 mm.

Weight:

approx. 45 g.

Scope of delivery:

Device, operating instructions.

Manufacturer:

Seneca s.r.l.. Italy

info Signalwandler-Broschüre
Signal converters and monitoring modules

You can download the handout Signal converter here.

Food

Quality control and traceability

Article no.Article descriptionAvailablePrice/ItemNumber
WK112000

Universal digital galvanic isolator WK112

on request
AccessoriesAvailablePrice/ItemNumber
WKBUS000

Supply terminal for 2 modules

on request
WKSUPPLY

Supply terminal for up to 75 devices

on request
= available from stock
= Delivery time approx. 1 week
= Please inquire about delivery time

Subject to prior sale