PM-50-Analog

Graphic display PM-50 with analog input

3.5" or 4.3" 18-bit color display with resistive touchscreen and swipe gesture
Universal input for process signals,
Thermocouple, resistance thermometer Pt100
Potentiometer input
WiFi 4 connectivity (ModbusTCP communication)

DatasheetTechnical supportRequest/On-site presentation
  • 3.5" or 4.3" 18-bit color display with resistive touchscreen
  • Parameterization on the device or via APP or web server
  • WiFi 4 connectivity (ModbusTCP communication)
  • Universal input for process signals, thermocouples, Pt100, potentiometer
  • RS485 interface and SSR driver outputs on board
  • Modular extensions possible

The new PM-50 graphic display with its universal analog input can be used with almost all commercially available temperature sensors, resistance thermometers and process signals, as well as programming, operating and control technologies for many applications. It is available with a 3.5" or 4.3" 18-bit (TFT) color display with resistive touchscreen and allows the user to easily switch between relevant screens by "swiping" to obtain comprehensive operating data for monitoring systems and products. Visual warnings and alarms are shown on the display, but can also be viewed via the PM-50 app on mobile devices. The app is available in the Apple and Google Play Store. A program wizard on the device makes it easy to set up the PM-50, but the display can also be programmed via the app or a web browser. For remote access to important workflows and process data, the display has an RS485 interface for Modbus RTU communication and Modbus TCP communication via WiFi (4th gen.). Thanks to the possibility of simple modular expansion of the display on site with the expansion modules, an RS232 interface for Modbus, an Ethernet connection (RJ45) and an analog output and/or relay output module (2x changeover contacts or 4x NO contacts) can be implemented quickly.

Entrance areas:

Thermocouple type:
K, S, R, J, T, N, B, E, C(W5/W26)
Temperature sensor (2- or 3-wire):
Pt100 alpha = .00385
Pt100 alpha = .00392
NI120 alpha = .00672
CU10 alpha = .00427
Voltage:
± 200 mVDC;
± 2 VDC;
± 20 VDC;
± 60 VDC
Current:
± 200 µADC;
± 2 mADC;
± 20 mADC;
± 200 mADC;
± 2 ADC
Potentiometer:
100 Ohm,
1000 Ohm,
10 KOhm

Accuracy:

Current input:
± 200 µADC = 0.12% + 0.04 µA
± 2 mADC = 0.12% + 0.4 µA
± 20 mADC = 0.12% + 4 µA
± 200 mADC = 0.12% + 0.40 µA
± 2 ADC = 0.7% + 0.4 mA

Voltage input:
± 200mVDC = 0.12% + 40 µV
± 2 VDC = 0.12% + 0.4 mV
± 20 VDC = 0.12% + 4mV
± 60 VDC = 0.12% + 40mV

All specifications refer to a temperature range of -10 °C to + 55°C.

Resolution:

Current input:
± 200 µADC = 10 nA
± 2 mADC = 0.1 µA
± 20 mADC = 1 µA
± 200 mADC = 10 µA
± 2 ADC = 0.1 mA

Voltage input:
± 200mVDC = 10 µV
± 2 VDC = 0.1 mV
± 20 VDC = 1 mV
± 60 VDC = 10 mV

A higher resolution can be achieved by input scaling.

Input impedance:

Current input:
± 200 µADC; ± 2 mADC; ± 20 mADC = 100 Ohm
± 200 mADC; ± 2 ADC = 0.06 Ohm

Voltage input:
All ranges 625 KOhm

Thermocouple:
20 MOhm

Display:

4.3" or 3.5" color TFT display with analog resistive touchscreen

3.5" display:
Colors: 262,144 K
Pixels: 320 x 240
Brightness: 540 cd/m²
LED backlight service life: 30,000h*

4.3" display:
Colors: 262,144 K
Pixels: 480 x 272
Brightness: 420 cd/m²
LED backlight service life: 30,000h*

*at room temperature (25 °C)

A/D conversion:

programmable from 5 to 200 measurements per second.

User inputs:

Two programmable user inputs
Max. Input voltage: 30 VDC

Sink:
Active: VIN < 0.9 VDC
Inactive: VIN > 2.4 VDC
20 KOhm pull-up at 3.3 V

Source:
Active: VIN > 2.4 VDC
Inactive: VIN < 0.9 VDC
20 KOhm pull-down

SSR outputs (OnBoard):

2 outputs, only SINK or SOURCE mode available, not separately adjustable.

Sink mode (NPN):
Type: Switched DC, N-channel open-drain MOSFET
Max: 100 mA
VDS ON: 0.3 V @ 100 mA
VDS MAX: 30 VDC
Leakage current in off-state: 0.5 mA max

Source mode (PNP):
Type: Switched DC, P-channel open-source MOSFET
Max: 100 mA
VDS ON: 0.3 V @ 100 mA
VDS MAX: 30 VDC
Leakage current in off-state: 0.5 mA max

Sensor supply:

24 VDC, ±5%; @max. 50 mA
Reference voltage: + 2 VDC, ± 2%
Reference current: 1.05 mADC, ± 2%

RS485 interface (OnBoard):

Uses the Modbus RTU protocol (RS485)
Baud rate: Up to 115,200
Data format: 7 or 8 bit; odd, even or no parity; 1 or 2 stop bits
Isolation: 500 Vrms to sensor, user voltage and digital inputs.
Not isolated to semiconductor outputs

Power supply:

10 VDC to 30 VDC; 4.6 W (without modules)
Max. Power consumption: 12 W (with modules)
Isolation: 500 Vrms for 1 min. to all inputs and outputs.

WiFi 4:

Output power up to 20.5 dBm
Frequency: 2412 MHz to 2484 MHz
Channels: 1 to 13
Note: Channel/frequency limitation is based on the configured country/region code.
Wi-Fi compliance: TCP/IP; 802.11 b/g/n

Modbus TCP communication via WiFi 4 possible.

Memory:

Non-volatile memory, retains all programmable parameters and display values
Memory card: microSD cards of up to 32 GB in FAT16/FAT32 format possible

Totalizer:

Time base: second, minute, hour or day
Batch counter: Can totalize measured values / Trigger: User input
Time accuracy: 0.01% typical
Decimal point: 0 to 0.0000
Scaling factor: 0.001 to 65.000
Display range: -199,999 to 999,999

Linearization:

Data point pairs: Selectable from 2 to 40
Display range: -199,999 to 999,999
Decimal point: 0 to 0.0000

Ambient conditions:

Operating temperature range: -10 °C to +55 °C
Storage temperature range: -20 °C to +60 °C
Humidity during operation and storage: 0 % to 85 % rH, non-condensing
Altitude: Up to 2000 meters

Vibration and shock:

Vibration: 5-500 Hz, 2 g
Shock: 20 g (10 g relay)

Dimensions (WxHxD):

PM500A0301600F00:
Installation dimensions (WxHxD): 44.8 mm x 44.8 mm x 87.17 mm
Height without terminal strips
Depth specification corresponds to basic device incl. rear cover
Installation depth with max. number of modules: 189.47 mm
Panel cut-out: DIN 45 x 45
Display/front (WxHxD): 95.09 mm x 82.09 mm x 14.25 mm
Rear cover (B): 11 mm

PM500A0400800F00:
Installation dimensions (WxHxD): 91.95 mm x 44.8 mm x 92.20 mm
Height without terminal strips
Depth specification corresponds to basic device incl. bus connector for PM-50 4.3"
Installation depth with max. number of modules: 160.40 mm
Panel cut-out: DIN 92 x 45
Display/front (WxHxD): 123.59 mm x 84.91 mm x 14.25 mm
Bus connector rear cover (B): 15 mm

Max. Sheet thickness: 6.35 mm
Min. sheet thickness for NEMA 4X/IP65 requirements: 1.02 mm

Housing:

One-piece cover/housing.
Flame retardant.
Installation seal and installation fastening included

Weight:

3.5" device: approx. 224 g
4.3": device approx. 321 g

Protection class:

Type 4X for indoor use only
IP65 (front)
IP20 (rear)

Certificates:

CE, UKCA, FCC, UL,

Scope of delivery:

PM500A0301600F00:
1x rear cover
2x 2x locking clip for shock and vibration applications
1x mounting frame

PM500A0400800F00:
1x empty module
1x Bus connector rear cover for PM-50 4.3" display
2x 2x locking clip for shock and vibration applications
1x mounting frame

Relay output (accessory):

PMM000I0RL200000:
2 x changeover contacts; switching capacity: 5 A at 250 VAC or 30 VDC; resistive load

PMM000I0RL400000:
4 x NO contacts;
Switching capacity: For one relay 3 A at 250 VAC or 30 VDC; resistive load
When using all relays switching capacity max. 1A/relay

Analog output (accessory):

PMM000I0AN000000:
0/4 mA to 20 mA or
0 VDC to 10 VDC
±10 VDC
Effec. Resolution: 16-Bit

RS232 interface (accessory)

PMM000CM23200000:
Possible baud rates: 300 to 115,200 bit/s
Data bits: 7 or 8
Parity: ungrade, grade or no parity

Ethernet interface (accessory):

PMM000CMENT00000:
10/100 T-Base
Auto MDI / MDI-X
RJ-45 socket
ModbusTCP communication possible.

AC supply (accessory):

PMM000PWACP00000:
Input: 85 VAC to 240 VAC; ±10%; 0.16 A to 0.3 A
Frequency: 50/60 Hz
Output: +15 VDC; ±10%; 0.8 A; max. 12 W
Insulation: 3 kV between primary and secondary side

Note:
The AC supply module must always be mounted in the last position of the communication flow.

Manufacturer:

Red Lion

Die Digitalanzeige neu definiert: PM-50
The digital display redefined: PM-50

Monitor your systems and your data like never before with the PM-50 graphical digital display.

Flyer PM-50 Wegweisende Entwicklung in der Digitalanzeigetechnik.
The PM-50 digital display

Pioneering development in digital display technology.
Decode your operating data without additional costs.

info Flyer Wachendorff Anzeigen
Wachendorff ads

Rules, displays and monitoring

info Flyer Einbaumessgeräte
Advertising brochure built-in measuring devices

Rules, displays and monitoring

Installation Guide PM-50 Analog
Installation instructions: PM-50 Analog

Installation Guide PM-50 Analog
Installation Guide: PM-50 Analog

PM-50 Digital Meter User Manual
PM-50 Analog Meter User Manual - English

PM-50A-Modbus-Register-Table
PM-50A Modbus Register Table

PM50 App iOs
PM50 App Android

Parameterize the PM-50 graphic display easily and conveniently via Android.
The app allows you to read, write, program and manage your PM50 display.

PM50 App iOs
PM50 App iOs

Parameterize the PM-50 graphic display easily and conveniently via iPhone or iPad.
The app allows you to read, write, program and manage your PM50 display.

Declaration of Conformity
Declaration of Conformity

PMM000CM23200000

RS232 interface module

RS232 interface module for the PM-50 base unit

PMM000CMENT00000

Ethernet interface module

Ethernet interface module for the PM-50 base unit

PMM000I0AN000000

Analog output module current/voltage

Analog output module for the PM-50 base unit

PMM000I0RL200000

Relay output module 2x changeover contact

Relay output module for the PM-50 base unit

PMM000I0RL400000

Relay output module 4x NO contact

Relay output module for the PM-50 base unit

PMM000PWACP00000

AC supply module

AC supply module for the PM-50 base unit

Article no.Article descriptionAvailablePrice/ItemNumber
PM500A0301600F00

Graphic display PM-50 with analog input, 3.5" display

on request
PM500A0400800F00

Graphic display PM-50 with analog input, 4.3" display

on request
AccessoriesAvailablePrice/ItemNumber
PMM000CM23200000

RS232 interface module for PM-50

on request
PMM000CMENT00000

Ethernet interface module for PM-50

on request
PMM000I0AN000000

Analog output module for PM-50

on request
PMM000I0RL200000

Relay output module for PM-50; 2x changeover contact

on request
PMM000I0RL400000

Relay output module for PM-50; 4x NC/NO contact

on request
PMM000PWACP00000

AC supply module for PM-50

on request
PMA000CP00800000

Bus connector for PM-50 4.3"

on request
PMA000MK00800000

Adapter kit for PM-50; 92 mm x 75 mm to 96 mm x 48 mm

on request
PMA000MK01600000

Adapter kit for PM-50; 68 mm x 68 mm to 96 mm x 48 mm

on request
PMA000MKMLP00000

Locking clip for shock and vibration applications

on request
PMA000SP00800000

Protective film for the display of the PM-50; 4.3" display (content 10 pieces)

on request
PMA000SP01600000

Protective film for the display of the PM-50; 3.5" display (content 10 pieces)

on request
= available from stock
= Delivery time approx. 1 week
= Please inquire about delivery time

Subject to prior sale

Prices exclude 19% VAT and shipping costs.