FnIO module - PROFINET fieldbus node NA9187
establishes the connection between the FnIO system and the PROFINET fieldbus
Delisting
If you have any questions, please contact our technical application consultants.
- Direct diagnostics via LEDs on the fieldbus node
- Replacement of modules when wiring is still in place
- Manages expansion modules with 1, 2, 4, 8 and 16 channels
- Simple termination (no resistor or end module required)
- Free combination of digital and analog I/O & special functions

As a slave, the NA9187 fieldbus node establishes the connection between the
the FnIO system and the PROFINET fieldbus.
The I/O modules used are automatically recognized and the fieldbus node
fieldbus node creates a local process image. The sequence of the
analog extension modules (data exchange word by word) and digital
extension modules (data exchange bit by bit) is arbitrary and can be
can be mixed. The internal process image of the fieldbus node
NA9197 is stored in the memory of the relevant controller via the PROFINET fieldbus.
responsible control unit. By dividing the process image into
process image into an input and output data area, the process data is
the process data is read in via the PROFINET, processed further in a
controller and the process output data is output via the PROFINET.
PROFINET.
The automatically generated process image is created in the order of the expansion
expansion modules in their slots.
If the number of digital I/Os exceeds 8 bits, an additional byte is
byte is started by the fieldbus node.
Power supply:
Supply voltage: 24 VDC nominal
Supply voltage range: 11 VDC to 28.8 VDC
Protection: Output current limitation (min. 1.5 A), reverse polarity protection
Power consumption:
115 mA typical at 24 VDC
Current consumption of the I/O module:
1.5 A at max. 5 V
Isolation:
Power supply of the internal logic: Not isolated
Power supply of the I/O driver: Isolated
Field performance:
Supply voltage: 24 VDC nominal
Supply voltage range: 11 VDC to 28.8 VDC
Max. Field power Contact:
10 ADC max.
Module dimensions (LxHxW):
45 mm x 99 mm x 70 mm
Node type:
Slave node (PROFINET)
Number of extensions for I/O slots:
max. 32 slots
Input variable:
max. 128 bytes
Output variable:
max. 128 bytes
Max. length of bus cable:
Up to 100 m from the Ethernet hub/switch with
twisted CAT3 UTP/STP
Max. Number of nodes:
limited by IP addresses
Baud rate:
100 Mbps
Protocol:
PROFINET I/O RT

GSD file for PROFINET
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.


Configuration software for FnIO modules
By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.


Here you can download our flyer "CODESYS - PLC - WebPanels a strong team for your application".