WZ113100

Universal monitor for analog signals WZ113100

DatasheetTechnical support
  • For current and voltage signals, Pt100, Pt500, Pt1000, Ni100 and thermocouples type J, K, R, S, T, E, B and N.
  • 2 relay outputs
  • Alarm value control with switch-on delay and hysteresis
  • Selectable alarm type (above and below and band alarm of the alarm value)
Signalwandler WZ113100

The WZ113100 universal monitor monitors an analog signal and switches one or two relays if the set limit value is exceeded or not reached. The alarm value control with switch-on delay and adjustable hysteresis makes the WZ113100 versatile. The device is simply snapped onto the top-hat rail for installation.

Entrance:

- Thermocouples J, K, R, S,T, E,Bund N.
- Temperature-dependent resistors (RTD) Pt100, Pt500, Pt1000, Ni100
- Potentiometer min. 1 kOhm to max. 100 kOhm.
- Voltage from 0 VDC to 10 VDC
- Current from 0 mA to +20 mA

Output:

2 NO relays (max. 3 A at 250 VAC).

Power supply:

10 VDC to 40 VDC or 19 VAC to 28 VAC 50/60 Hz, typically 2.5 W, max. 3 W

Accuracy:

0.1 % in relation to the measuring range of the input.

Settings:

- Limit values between 1 % and 100 % of the signal.
- Switch-on delay freely adjustable.
- Hysteresis freely adjustable.
All settings are made using the free parameterization software
EASYSETUP parameterization software.

Short-circuit resistance:

1.5 kV between supply / input.
3 kV between the input/power supply and outputs.

Ambient conditions:

Relative humidity: 30 % to 90 % at 40 °C non-condensing
Operating temperature: -10 °C to +65 °C

Safety:

EN61010-1:2013-10

EMC:

EN61000-6-2:2006-10
EN61000-4-4:2013-01
EN61000-6-4:2007-11 + A1:2013-01
EN61000-4-5:2015-05
EN61000-4-2:2011-04
EN61000-4-6:2014-09
EN61000-4-3:2007-04 + A1:2009-01 + A2:2011-01
EN61000-4-11:2006-02

Connection:

Plug-in screw terminals.

Housing:

Flame-retardant and stable polycarbonate housing.

Protection:

IP20

Dimensions (WxHxD):

17.5 mm x 100 mm x 112 mm

Weight:

approx. 200 g.

Scope of delivery:

Device, operating instructions

Manufacturer:

Seneca s.r.l.

info Signalwandler-Broschüre
Signal converters and monitoring modules

You can download the handout Signal converter here.

sw easy setup
Easy Setup

Configuration software for signal converters.

By downloading and using software and apps from this website, I agree to the GTC and the supplementary software clause.

BA WZ113-1
WZ113100- Universal monitor

Food

Quality control and traceability

Vertriebsteam
Für vertriebliche Fragen
Angebot, Produkte, Auftrag und Lieferzeiten
Please contact:
Unseren Vertriebsinnendienst
Für Fragen im Rahmen der Auftragsabwicklung
Auftragsbestätigung, Liefertermin, Rechnung
Please contact:
Unsere Auftragsabwicklung
supportteam
Für technischen Support
im Rahmen der Inbetriebnahme, Projektierung, Konfiguration, etc.
Please contact:
Technischer Support: Mo. bis Do. von 8:00 Uhr bis 16:00 Uhr und Fr. von 8:00 Uhr bis 15:00 Uhr
Article no.Article descriptionAvailablePrice/ItemNumber
WZ113100

Universal monitor with 2 relays

134,00 €
AccessoriesAvailablePrice/ItemNumber
KABUSBM2

USB programming cable, USB 2.0A to micro USB, 2 m cable

9,00 €
= available from stock
= Delivery time approx. 1 week
= Please inquire about delivery time

Subject to prior sale

Prices exclude 19% VAT and shipping costs.