WT121

2-wire - Loop Powered universal signal converter WT121

DatasheetTechnical supportRequest/On-site presentation
  • Converts a Pt100/500/1000, Ni100, thermocouple or voltage signal into 4 to 20 mA, 20 to 4 mA
  • 16 bit resolution (high accuracy)
  • Supply from the current loop 7 VDC to 30 VDC
  • Simple commissioning via software
  • Quick installation thanks to spring terminals
2-Draht - Loop Powered Universalsignalwandler WT121

The WT121 signal converter converts the signals of a Pt100, Pt500, Pt1000, Ni100, thermocouple or a voltage signal into a 4 mA to 20 mA or 20 mA to 4 mA standard signal. The signal converter is supplied from the current loop. The output signal is linearly proportional to the input.
The signal converter can be fully adjusted via software before installation and is immediately ready for operation. No power supply is required for programming via the software, as this is done via the programming plug.

Entrance:

Pt100 from -200 °C to +650 °C in 2-, 3- or 4-wire technology;
Ni100 from -60 °C to +250 °C in 2-, 3- or 4-wire technology;
Pt500 from -200 °C to +650 °C in 2-, 3- or 4-wire technology;
Pt1000 from -200 °C to +200 °C in 2-, 3- or 4-wire technology;
Thermocouple type: S,T,J,N,K,E,R,B;
Potentiometer: 500 Ohm to 1700 Ohm (up to 100 kOhm with external parallel resistor);
Voltage: -150 mV to +150 mV; adjustable via software.

Resolution:

16 bit

Output:

4 mA to 20 mA or 20 mA to 4 mA, adjustable via software.

Supply:

7 VDC to 30 VDC from the current loop.

Accuracy:

+/-0.1 % of the measuring range or 0.1 °C.

Mains filter:

50 Hz / 60 Hz

Response time:

< 620 msec (with active mains filter)

Temperature coefficient:

< 100 ppm (30 ppm typical)

Sampling rate:

300 msec (with active mains filter)

Ambient conditions:

30 % to 90 % relative humidity at 40 °C
Operation: -40 °C to +85 °C
Storage: -40 °C to +105 °C

Safety:

EN61010-1:2013-10

EMC:

EN61000-6-2:2006-10
EN61000-4-4:2013-01
EN61000-6-4:2007-11 + A1:2013-01
EN61000-4-5:2015-05
EN61000-4-2:2011-04
EN61000-4-6:2014-09
EN61000-4-3:2007-04 + A1:2009-01 + A2:2011-01
EN61000-4-11:2006-02

Connection type:

Spring terminals from 0.2 to 2.5 mm²

Protection class:

IP20

Housing:

Sturdy plastic housing PBT

Weight:

approx. 28 g

Scope of delivery:

Device, operating instructions

Manufacturer:

SENECA S.r.l.

info Signalwandler-Broschüre
Signal converters and monitoring modules

You can download the handout Signal converter here.

Food

Quality control and traceability

Manual WT121
WT121 - 2-wire loop-powered and insulated transmitter for thermoresistance and thermocouple

Article no.Article descriptionAvailablePrice/ItemNumber
WT121000

2 wire loop powered universal signal converter

on request
AccessoriesAvailablePrice/ItemNumber
WS117P00

WS117P Software / Cable Kit

on request
= available from stock
= Delivery time approx. 1 week
= Please inquire about delivery time