DIN rail power supply unit PS24V25AB
3-phase input: 400 VAC to 500 VAC
Output: 24 VDC up to 60 °C operating temperature
3 different output protection modes,
1 overload and overvoltage protection.
- 3-phase input: 400 VAC to 500 VAC
- Output: 24 VDC up to 60 °C operating temperature
- Flexible output power from 480 watts to 600 watts
- Robust metal housing with top-hat rail mounting
- High overload without shutdown; up to 50
- 3 different protection modes for the output
- Relay output for output voltage monitoring

The PS24V25AB power supply unit is a high-quality 3-phase switched-mode power supply unit for DIN rail mounting. It impresses with its compact and intelligent design as well as its robust metal housing. The output voltage is easy and simple to adjust (22 VDC to 27 VDC) and is highly stable even with temperature fluctuations and load changes.
In addition to short-circuit protection with 3 different output protection modes, overload and overvoltage protection as well as a monitoring relay at the output ensure a high level of safety. The output power can be easily increased by connecting additional PS24V25AB power supply units of the same type in parallel.
Entrance:
Nominal input voltage: 400 VAC to 500 VAC
Input voltage range: 330 VAC to 550 VAC
Frequency range: 47 to 63 Hz
Inrush current (Vn and In load) I²t: ≤ 35 A ≤ 5 msec.
Input current (400 to 500 VAC at 40 °C): 1.27 A to 1.01 A
Internal fuse: T6.3 A
External fuse (recommended): 16 A (B characteristic)
Output:
Output voltage (Vn) Factory setting +/-3 %: 24 VDC
Adjustment range output voltage (Vadj): 22 VDC to 27 VDC
Start with large load (capacitive load): ≤ 50,000 μF
Switch-on delay after applying supply: 1 sec (max.)
Continuous current at 24 VDC < 40 °C (In): 25 A (permanent)
Continuous current at 24 VDC < 50 °C (In): 22 A (permanent)
Continuous current at 24 VDC < 60 °C (In): 20 A (permanent)
Power boost current at 24 VDC / 60 °C (In): In (60 °C) x 1.5 ≥ 3 Min.
Max. Current at overload approx. 4 VDC (perm.): Imax = In 60 °C x (1.8 to 2.2)
Max. Max. current for short circuit (Icc): 60 A
In hiccup mode max. 2 seconds: 60 A
Continuous mode: 60 A
Hold-up time (min. VAC) Vn In 40 °C : typically 20 milliseconds
Remaining residual ripple: ≤ 80 mVpp
Efficiency: ≥ 91 %
Overtemperature protection: Yes, switching off the output and automatic
restart of the module.
Short-circuit protection at the output (adjustable via jumper):
A. Manual reset
B. Hiccup mode (cyclical clocking of the output until the short circuit is eliminated)
C. Reset when power supply is reconnected (output switches off until power supply unit is restarted)
Maximum power dissipation at 40 °C: 54 watts
Overload protection: Yes
Overvoltage protection at the output: Yes (typically 35 VDC)
Parallel operation possible: Yes
Protective relay: For DC 1 A at 30 VDC with resistive load
For AC 1 A at 60 VAC with resistive load
Min. permissible load: Min. 1 mA at 5 VDC
Isolation:
Input/output insulation voltage: 3,000 VAC
Insulation voltage input/PE: 1,605 VAC
Insulation voltage output/PE: 500 VAC
Standards and approvals:
CE according to EMC 2004/108/EC and Low Voltage Directive 2006/95/EC,
UL approval according to UL508, RoHs compliant
Reliability:
MTBF according to IEC 61709 > 500,000 hours
Protection class:
IP20
Housing:
Sturdy metal housing. Mounting on the top-hat rail
Dimensions (WxHxD): 85 mm x 120 mm x 140 mm.
Connection:
Fixed terminal strips with 4 mm² cross-section (30 to 10 AWG)
Relative humidity:
max. 95 %. RF at 25 °C, non-condensing.
Ambient temperature:
Operation: -25 °C to +70 °C
( > 60 °C leads to a reduction of the operating values by 2.5 %/ °C ).
Storage: -40 °C to +85 °C.
Weight:
approx. 750 g
Scope of delivery:
Device, operating instructions.
Manufacturer:
ADEL System s.r.l., Italy