ECM6-E-MID

Energy meter 6 A Modbus TCP ECM6-E-MID

This product has been discontinued.
Three-phase energy meter for transformer measurement

DatasheetTechnical supportRequest/On-site presentation
  • Certified MID version
  • For Ethernet communication (Modbus TCP)
  • For 1 or 5 A transducers
  • Programmable transformer ratio
  • Fully bidirectional four-quadrant measurements for all energies and powers
  • For 4-wire networks with balanced or unbalanced load
  • Class B according to EN 50470-3
  • S0 output for energy pulse output
Energiezaehler-ECM6-E-2

The ECM6-E-MID is a three-phase energy meter that has MID conformity certification and is therefore suitable for billing purposes. The meter can be operated with 1 A and 5 A transformers, has a programmable wandering ratio and can carry out complete bidirectional four-quadrant measurements for all energies and outputs. It is suitable for 4-wire networks with balanced or unbalanced load and fulfills the accuracy of class B according to EN 50470-3. In addition to the standard S0 interface, the energy meter variant mentioned here has an Ethernet interface with the Modbus TCP protocol and provides a web server.

MID conformity

Yes

Auxiliary voltage

From measuring circuit Un ±20%

Consumption

7.5 VA 0.5 W

Dimensions (W x H x D)

72 mm x 90 mm x 64 mm

Weight

450 g

Operating temperature range

Operation -25 °C to 55 °C

Storage temperature range

Storage -25 °C to 75 °C

Application range relative humidity

Humidity 0 to 80 RH

Assembly

DIN rail mounting

Electrical connection

4 Ladder

Display type

LCD

Display number of digits

8

Display IP protection class

IP51 (front), IP20 (terminal)

Measuring inputs Conductor cross-section

1.5 mm² to 6 mm²

Tariff outputs Conductor cross-section

0.14 mm² to 2.5 mm²

Tariff input

No

Voltage range Tariff

None

Metrological LED pulse value

10000 imp. / kWh

Measuring LED pulse duration

10 ± 2 ms

Communication

S0, Modbus TCP (10 / 100 Mbps)

Web server

Yes

Data storage

8 MB

Active energy Accuracy

Class B according to EN 50470-3

Reactive energy accuracy

Class 2 according to IEC/EN 62053-23

Starting current

2 mA

Minimum current

10 mA

Transition current

50 mA

Rated current

0 to 6 A

Rated current

1 A

Rated current - load

< 0.04 VA

Frequency measurement

50 to 60 Hz

Number of S0 outputs

1

S0 output Maximum current

27 mA

S0 output Maximum voltage

27 DC

S0 output Pulse output

100 Imp. / kWh

S0 output Pulse duration On

50 ± 2 ms

S0 output Pulse duration Off

30 ± 2 ms

Scope of delivery

Counter, manual

Manufacturer

Celsa Messgeräte GmbH

Schnittstellenbeschreibung Modbus ECM/WECM
Interface description Modbus ECM/WECM

Energiedatenerfassung
Energy data acquisition

... You can only optimize what you measure!

Energiezähler 20200810
Energy meter

Overview of product variants