ECM6-M-MID

Energy meter 6 A M-Bus ECM6-M-MID

This product has been discontinued.
Three-phase energy meter for transformer measurement

DatasheetTechnical supportRequest/On-site presentation
  • Certified MID version
  • For M-Bus communication
  • For 1 or 5A transformer
  • Programmable transformer ratio
  • Fully bidirectional four-quadrant measurements for all energies and powers
  • For 3- / 4-wire networks with balanced or unbalanced load
  • Class B according to EN 50470-3
  • S0 output for energy pulse output
Energiezähler 6 A M-Bus ECM6-M-MID

The ECM6-M-MID is a three-phase energy meter that has MID conformity certification and is therefore suitable for billing purposes. The meter can be operated with 1 A and 5 A transformers, has a programmable wandering ratio and can carry out complete bidirectional four-quadrant measurements for all energies and outputs. It is suitable for 3/4-wire networks with balanced or unbalanced load and fulfills the accuracy requirements of class B according to EN 50470-3. In addition to the standard S0 interface, the version of the energy meter mentioned here has an RS232 interface with the M-BUS protocol.

MID conformity

Yes

Auxiliary voltage

From measuring circuit Un ±20%

Consumption

7.5 VA 0.5 W

Dimensions (W x H x D)

72 mm x 90 mm x 64 mm

Weight

410 g

Operating temperature range

Operation -25 °C to 55 °C

Storage temperature range

Storage -25 °C to 75 °C

Application range relative humidity

Humidity 0 to 80 RH

Assembly

DIN rail mounting

Electrical connection

3/4 ladder

Display type

LCD

Display number of digits

8

Display IP protection class

IP51 (front), IP20 (terminal)

Measuring inputs Conductor cross-section

1.5 mm² to 6 mm²

Tariff outputs Conductor cross-section

0.14 mm² to 2.5 mm²

Tariff input

Yes

Voltage range Tariff

80 - 276 AC-DC

Metrological LED pulse value

10000 imp. / kWh

Measuring LED pulse duration

10 ± 2 ms

Communication

S0, M-Bus (300 - 38400 bit/s)

Web server

None

Data storage

8 MB

Active energy Accuracy

Class B according to EN 50470-3

Reactive energy accuracy

Class 2 according to IEC/EN 62053-23

Starting current

2 mA

Minimum current

10 mA

Transition current

50 mA

Rated current

0 to 6 A

Rated current

1 A

Rated current - load

< 0.04 VA

Frequency measurement

50 to 60 Hz

Number of S0 outputs

1

S0 output Maximum current

27 mA

S0 output Maximum voltage

27 DC

S0 output Pulse output

100 Imp. / kWh

S0 output Pulse duration On

50 ± 2 ms

S0 output Pulse duration Off

30 ± 2 ms

Scope of delivery

Counter, manual

Manufacturer

Celsa Messgeräte GmbH

Schnittstellenbeschreibung M-Bus ECM-WECM
Interface description M-Bus ECM/WECM

Energiedatenerfassung
Energy data acquisition

... You can only optimize what you measure!

Energiezähler 20200810
Energy meter

Overview of product variants