Energy meter 6 A M-Bus ECM6-M-MID
This product has been discontinued.
Three-phase energy meter for transformer measurement
- Certified MID version
- For M-Bus communication
- For 1 or 5A transformer
- Programmable transformer ratio
- Fully bidirectional four-quadrant measurements for all energies and powers
- For 3- / 4-wire networks with balanced or unbalanced load
- Class B according to EN 50470-3
- S0 output for energy pulse output

The ECM6-M-MID is a three-phase energy meter that has MID conformity certification and is therefore suitable for billing purposes. The meter can be operated with 1 A and 5 A transformers, has a programmable wandering ratio and can carry out complete bidirectional four-quadrant measurements for all energies and outputs. It is suitable for 3/4-wire networks with balanced or unbalanced load and fulfills the accuracy requirements of class B according to EN 50470-3. In addition to the standard S0 interface, the version of the energy meter mentioned here has an RS232 interface with the M-BUS protocol.
MID conformity
Yes
Auxiliary voltage
From measuring circuit Un ±20%
Consumption
7.5 VA 0.5 W
Dimensions (W x H x D)
72 mm x 90 mm x 64 mm
Weight
410 g
Operating temperature range
Operation -25 °C to 55 °C
Storage temperature range
Storage -25 °C to 75 °C
Application range relative humidity
Humidity 0 to 80 RH
Assembly
DIN rail mounting
Electrical connection
3/4 ladder
Display type
LCD
Display number of digits
8
Display IP protection class
IP51 (front), IP20 (terminal)
Measuring inputs Conductor cross-section
1.5 mm² to 6 mm²
Tariff outputs Conductor cross-section
0.14 mm² to 2.5 mm²
Tariff input
Yes
Voltage range Tariff
80 - 276 AC-DC
Metrological LED pulse value
10000 imp. / kWh
Measuring LED pulse duration
10 ± 2 ms
Communication
S0, M-Bus (300 - 38400 bit/s)
Web server
None
Data storage
8 MB
Active energy Accuracy
Class B according to EN 50470-3
Reactive energy accuracy
Class 2 according to IEC/EN 62053-23
Starting current
2 mA
Minimum current
10 mA
Transition current
50 mA
Rated current
0 to 6 A
Rated current
1 A
Rated current - load
< 0.04 VA
Frequency measurement
50 to 60 Hz
Number of S0 outputs
1
S0 output Maximum current
27 mA
S0 output Maximum voltage
27 DC
S0 output Pulse output
100 Imp. / kWh
S0 output Pulse duration On
50 ± 2 ms
S0 output Pulse duration Off
30 ± 2 ms
Scope of delivery
Counter, manual
Manufacturer
Celsa Messgeräte GmbH